VisFlow60

Containermodul med VisBlue logo

Data sheet

SIZE AND MASS
Container size:
20 [ft]
Footprint:
2440 x 6060 [mm] (W x D)
Height: 
2590 [mm]
Weight: 
29700 [kg]
Design life:
20,000/20 [cycles/year]

CAPACITY AND POWER
Peak power charge/discharge:
1,1 x nominal power. 5 min. on/off
DC Efficiency (Stack):
87 [%] DC round trip Includes both charge/discharge efficiency. Depending on load profile.
AC efficiency (system) @ rated power:
67 [%]. AC roundtrip includes both charge/discharge efficiency. Depending on load profile.
DC voltage:
40 to 60 [V]
AC voltage:
1 x 230 // 3 x 400 50Hz [VAC]
Grid connection:
1 to 3 [phase(s)]
Depth of Charge/Discharge: 
3 to 80%
Response time:
<20 [ms]
Self-discharge:
<0.3% of full capacity per day (pumps stopped). <100Wh per day for 33kWh systems

REMOTE ACCESS
Communication:
Remote access through LAN with open control through Modbus TCP (address list upon request)
Battery control:
Charge/discharge is controlled by input from energy meter. Charging/discharging is controlled by input from external master.

ENVIRONMENT
Electrolyte temperature:
0 to +35 [°C]
Humidity:
95% RH non-condensing
Ventilation:
Depending on installation location. Cooling/heating can be installed.
Safety:
Non-flammable and non-explosive due to water-based electrolyte

More facts